German Drinking Water Ordinance: which version applies and which limit values
GuideWater knowledge

German Drinking Water Ordinance: which version applies and which limit values

The German Drinking Water Ordinance of 20 June 2023 applies unchanged. Four new provisions from it have taken effect since 12 January 2026. All limit values in a table.

The Trinkwasserverordnung (German Drinking Water Ordinance) currently in force dates from 20 June 2023 and has remained unchanged since it was issued. Anyone looking for a 2025 or 2026 version is looking for something that does not exist. What has changed is something else: on 12 January 2026, four provisions of the Ordinance took effect, including the first limit value for per- and polyfluoroalkyl substances (PFAS) and the end of lead pipes. The following overview shows the current legal position, all 33 limit values in a table and the five dates on which further values will become stricter.

Which version applies

The Ordinance's full official citation is “Trinkwasserverordnung vom 20. Juni 2023 (BGBl. 2023 I Nr. 159, S. 2)”. The official text contains no note of amendments. So nothing in the Ordinance has been changed since the text record of 24 June 2023. In July 2026, it applies in exactly the version in which it was enacted.

The addition “2023” is not an official designation. The Ordinance is simply called Trinkwasserverordnung, abbreviated to TrinkwV. The year has become established to distinguish it from the Trinkwasserverordnung 2001. That was the version it replaced.

In legal terms, the Ordinance transposes Directive (EU) 2020/2184, the EU Drinking Water Directive of 16 December 2020, into German law. The official text expressly points this out. This is also where the Europe-wide uniform dates on which individual limit values take effect come from. 12 January crops up again and again in the Ordinance, with years varying from 2024 to 2036.

Its size is the most visible difference from its predecessor. The Ordinance has 72 sections in 16 parts, plus seven annexes. The TrinkwV 2001 made do with 25 sections.

What has applied since 12 January 2026

Four provisions came into force on 12 January 2026. All four were already in the text in 2023, with a later date of application.

The first limit value for PFAS. Since 12 January 2026, a limit value of 0.00010 mg/l has applied to the sum of PFAS-20. This refers to the sum of 20 per- and polyfluoroalkyl substances listed by name in Annex 2, including perfluorooctanoic acid (PFOA) and perfluorooctane sulfonic acid (PFOS). Measured values below the limit of quantification are not counted when calculating the sum. Each individual substance must be reported separately. Where PFAS in water come from is explained in the guide to PFAS in drinking water.

Haloacetic acids. A limit value of 0.060 mg/l applies to the sum of HAA-5. This covers five reaction products formed during the disinfection or oxidation of water: monochloroacetic, dichloroacetic and trichloroacetic acid as well as monobromoacetic and dibromoacetic acid. A supplier may dispense with testing if it disinfects without treatment substances that form HAA-5.

Microcystin-LR. Since 12 January 2026, this liver toxin produced by cyanobacteria has had a limit value of 0.0010 mg/l. The letters LR stand for leucine and arginine, two amino acids that distinguish it from other microcystins. Testing is only required if potentially toxic cyanobacteria occur in the water source, for example during an algal bloom.

The end of lead pipes. Lead pipes had to be removed or decommissioned by the end of 12 January 2026. Since 13 January 2026, there has also been an obligation to provide proof to consumers.

All limit values in a table

The Ordinance classifies the chemical parameters according to whether their concentration can increase on the way through the network and the domestic installation. Annex 2 Part I lists 18 substances whose concentration does not normally increase any further. Part II lists 15 substances for which an increase is possible. This division determines where measurements are taken and who is answerable for the value.

Chemical parameters from the waterworks

The following 18 values are determined during abstraction and treatment. All figures in mg/l.

ParameterLimit valueNote
Acrylamide0,00010based on the residual monomer concentration
Benzene0,0010
Boron1,0
Bromate0,010
Chromium0,025until 11 January 2030, then 0.0050
Cyanide0,050
1,2-Dichloroethane0,0030
Fluoride1,5
Microcystin-LR0,0010since 12 January 2026, only if cyanobacteria are present
Nitrate50Note the sum formula with nitrite
Pesticides (individual)0,00010Aldrin, dieldrin, heptachlor, heptachlor epoxide 0.000030 each
Total pesticides0,00050Sum of the individual substances detected
Sum of PFAS-200,00010since 12 January 2026
Sum of PFAS-40,000020from 12 January 2028
Mercury0,0010
Selenium0,010
Tetrachloroethene and trichloroethene0,010Sum of both substances
Uranium0,010

Nitrate has a special feature that is often overlooked. In addition to the limit value of 50 mg/l, a sum formula applies. The nitrate concentration divided by 50 plus the nitrite concentration divided by 3 must not exceed the value 1. Water with 45 mg/l nitrate and 0.3 mg/l nitrite complies with both individual limit values and yet still violates the sum formula. How nitrate gets into groundwater is explained in the guide to nitrate in groundwater and drinking water. There is a separate guide on pesticides, covering plant protection products in tap water.

Chemical parameters from the domestic installation

The following 15 values can increase in the distribution network and in the drinking water installation. They are determined in the building, not at the waterworks. All figures in mg/l.

ParameterLimit valueNote
Antimony0,0050
Arsenic0,010until 11 January 2028, staggered down to 0.0040
Benzo(a)pyrene0,000010
Bisphenol A0,0025since 12 January 2024
Lead0,010until 11 January 2028, then 0.0050
Cadmium0,0030
Chlorate0,0700.20 with intermittent dosing
Chlorite0,20
Epichlorohydrin0,00010based on the residual monomer concentration
Haloacetic acids (HAA-5)0,060since 12 January 2026
Copper2,0
Nickel0,020
Nitrite0,500.10 at the waterworks outlet
Polycyclic aromatic hydrocarbons0,00010Sum of four individual substances
Trihalomethanes (THM)0,050Sum of four reaction products

A strict measurement rule applies to lead, copper, nickel and arsenic. In staggered stagnation sampling, three samples are taken, designated S0, S1 and S2. If any one of them is above the limit value, the limit is deemed to have been exceeded. So a favourable average does not save the measurement. The same applies to a random sample.

Chlorate and chlorite come from disinfection and therefore have flexible values. For chlorate, 0.070 mg/l applies as standard, 0.20 mg/l with intermittent dosing, and 0.70 mg/l is permitted for short periods to avert a hazard. If measured at the waterworks outlet, a reference value of 0.020 mg/l applies. How chlorine is used in drinking water is explained in the guide to chlorine in drinking water.

Microbiological parameters and indicator parameters

Annex 1 governs the microbiological requirements. Escherichia coli and intestinal enterococci must not be detectable in 100 ml of drinking water; the value for both is 0 per 100 ml.

Annex 3 lists the indicator parameters, which describe the water's characteristics rather than health aspects. These include sulphate at 250 mg/l and turbidity at 1.0 nephelometric turbidity units. The pH value must be between 6.5 and 9.5. For Legionella spec., Annex 3 Part II sets a technical action value of 100 colony-forming units per 100 ml.

Somatic coliphages have been newly added, with a reference value of 50 plaque-forming units in raw water. Somatic coliphages are viruses that infect bacteria. Their detection indicates whether viruses can get into a water supply, closing a gap in the old Ordinance. More about the germs themselves can be found in the guide to bacteria in tap water.

What the revision changed

The increase from 25 to 72 sections is mainly due to a new approach introduced by the revision. The old Ordinance only checked water quality at the tap. The current version additionally requires the entire route to be safeguarded, from the catchment area through treatment to the domestic installation. Part 7 calls this the risk-based approach.

In practice, this means mandatory risk management for water supply systems. Instead of simply taking samples, the operator must systematically identify and assess hazards and derive measures from them. The deadlines for this are staggered. Large systems supplying more than 100 cubic metres per day or more than 500 people must have completed this by the end of 12 January 2029. For smaller systems, the deadline runs until 12 January 2033.

Transparency obligations are also new. Every supplier must publish its analysis values online without a connected customer or consumer having to ask for them. What exactly has to be published there is explained in the guide to the origin and treatment of our drinking water.

The limit values themselves have changed in nine places: three substances tightened, six newly added. Lead, arsenic and chromium were tightened, each with transition periods. Newly added are bisphenol A, chlorate, chlorite, haloacetic acids, microcystin-LR and PFAS.

Treatment is also more tightly regulated. § 19 paragraph 2 prohibits adding substances other than treatment substances to raw water or drinking water. Under paragraph 3, only substances and disinfection methods from the list under § 20 are permitted. The list is kept by the Umweltbundesamt (German Environment Agency). Under paragraph 6, treatment substances must subsequently be removed again. An exception applies to substances that are intended to remain in the drinking water. Only unavoidable residues remain permissible. They must have no technological effect and be harmless to health.

Lead pipes: deadline expired

§ 17 regulates lead drinking water pipes in six paragraphs. The core provision is in paragraph 1: the operator of a water supply system had to remove or decommission existing lead pipes or sections of them by the end of 12 January 2026. In a rented building, the operator is the owner.

The Ordinance provides for two extensions. Under paragraph 2, the public health office can extend the deadline if the operator commissioned a registered installation company before 12 January 2026. The company must certify that, for capacity reasons, the job will only be completed later.

Paragraph 3 allows an extension until the end of 12 January 2036 at the latest. For this, three conditions must be met at the same time. First, it is a building water supply system or a private water supply system. Second, the water is used only in one's own household. Third, there is no reason to fear harm to the health of the regular users, particularly with regard to age and sex. If minors, pregnant women or women of childbearing age move in, the operator must report this without delay. If ownership changes, the extended deadline ends one year after the transfer.

For tenants, paragraph 5 is the most important. Since 13 January 2026, the operator has had to declare to affected consumers in text form, and prove in a suitable manner, that it has removed the lead pipes or holds an extension of the deadline. Anyone who lives in an old building and has doubts can request this proof.

Paragraph 6 obliges water supply and installation companies to report any lead pipes they find to the public health office without delay. Under paragraph 4, the operator must also prove to the public health office, without being asked, that it has fulfilled its obligation.

A common misconception concerns the terminology. It is steel pipes that are galvanised; lead is a pipe material in its own right. So there is no such thing as galvanised lead pipes. Lead can be recognised by its soft, grey surface, which can be scratched with a knife, and by the dull sound it makes when tapped. Why lead is particularly critical for children is explained in the guide to heavy metals in tap water.

Legionella and the technical action value

For legionella, the ordinance deliberately sets no limit value but a technical action value of 100 colony-forming units per 100 ml. The difference is more than a matter of wording: a limit value marks the boundary of what is permissible, whereas a technical action value triggers obligations to act.

§ 51 defines the threshold precisely. If the action value is reached, the operator must act without delay. It reports the finding to the public health office, investigates the causes, including an on-site inspection, and prepares a written risk assessment in line with the recommendation of the Umweltbundesamt (German Environment Agency). The value does not need to be exceeded; reaching it is enough.

This applies to drinking water installations with large-scale water heating systems, as are common in blocks of flats. Legionella multiply most readily between 25 and 45 °C, which is why temperature management in the hot water tank determines the risk. How this can be solved technically is explained in the guide to the legionella filter.

Who is liable for what

Responsibility changes hands at a clear line: the water supplier is liable up to the house connection, and from there the owner bears responsibility for the drinking water installation. The owner's pipes, fittings and storage tanks determine the values of the 15 parameters from Annex 2 Part II that can rise within the building.

§ 10 calls the point at which the requirements must be met the point of compliance. For water supplied through pipes in buildings, it is at the outlet of the drinking water draw-off points, i.e. at the tap. This reference point at the tap explains why sampling at the waterworks alone says little about your own water.

This is precisely why Annex 2 divides the chemical parameters into two parts. Everything in Part II can rise within the building: lead, copper and nickel from pipes and fittings, bisphenol A from materials, trihalomethanes from disinfection. A good value at the waterworks is of little help with these if the last few metres contaminate the water again.

The obligations for landlords follow from this division. Anyone who supplies drinking water as part of a commercial activity operates a water supply system within the meaning of the ordinance, and letting property counts as such an activity. This gives rise to testing obligations, including legionella testing for large-scale water heating systems, as well as notification obligations towards the public health office and information obligations towards tenants. Testing may only be carried out by a testing laboratory approved under § 40.

What the Ordinance leaves open

Three much-discussed groups of substances have no limit value in the annexes: pharmaceutical residues, hormones and microplastics. For them, there is no value whose exceedance triggers measures, and they are not measured across the board either.

Nevertheless, the ordinance does have an instrument for substances without a limit value. § 35(1) no. 7 requires risk management to cover the substances on the European watch list. What counts is the version of the list in force at any given time under Article 13(8) of Directive (EU) 2020/2184. Through the list, substances can come under consideration before a limit value exists for them.

The reason for the gap lies in wastewater treatment. For micropollutants such as pharmaceutical residues, a fourth treatment stage would be needed in wastewater treatment plants, for example with ozonation or activated carbon. In Germany, the majority of wastewater treatment plants operate with three stages. What is known about pharmaceutical residues is explained in the guide to pharmaceutical residues in tap water.

Anyone who wants to reduce micropollutants in their own household relies on adsorption. Activated carbon binds organic compounds, chlorine and substances that affect taste to its surface. This does not apply to dissolved minerals and salts; their concentration remains unchanged. What activated carbon can do and where its limits lie is explained in the guide to the activated carbon filter for water.

How to get the values for your own water

The 33 limit values above apply uniformly nationwide, but the actual measured values depend on the supply area. The supplier must publish them online. Searching for the supplier's name together with the term “drinking water analysis” usually leads straight to the table.

The supplier's analysis says little about the last few metres inside the building. Lead, copper and nickel levels are determined by your own plumbing, and measuring them requires a sample from your own tap taken by an approved testing laboratory. Which methods are available and what they cost is explained in the guide to measuring water quality. The guide to substances in tap water gives an overview of all dissolved substances.

The next deadlines

Five dates are still to come. All of them stem from the current version; no new ordinance is required for them.

DateWhat takes effect
12 January 2028Lead drops to 0.0050 mg/l, sum of PFAS-4 at 0.000020 mg/l is added, arsenic 0.0040 mg/l for newly commissioned systems
12 January 2029Risk management for systems with over 100 cubic metres per day or over 500 people
12 January 2030Chromium drops from 0.025 to 0.0050 mg/l
12 January 2033Risk management for systems with 10 to 100 cubic metres per day or 50 to 500 people
12 January 2036Arsenic 0.0040 mg/l for all water supply systems

The staggered arsenic limits illustrate the pattern. Until 11 January 2028, 0.010 mg/l applies to all systems. Systems newly commissioned from 12 January 2028 must meet 0.0040 mg/l straight away. Older systems may remain at the old value until 11 January 2036. From 12 January 2036, the stricter value applies without exception.

Conclusion

The Drinking Water Ordinance has been in force unchanged since 20 June 2023, and yet in 2026 it is a different ordinance from the one in 2023. Four provisions took effect on 12 January 2026, and five further dates will follow up to 2036. Anyone who wants to know what applies today should therefore check the date of application in Annex 2 rather than the year of publication.

Two points are of direct benefit to consumers. First, proof regarding lead pipes, which consumers have been able to request since 13 January 2026. Second, the supplier's analysis, which must be available online. For everything beyond the house connection, your own plumbing remains decisive.

Alb Filter Fusion under-sink bundle with one year of free cartridges

Related to this topic

Alb Filter FUSION – activated carbon and Nano filtration combined

The FUSION under-sink drinking water filter combines a sintered activated carbon block with Nano ultrafiltration. Among other things, it reduces chlorine, microplastics, hormones, heavy metals and germs, and leaves the minerals in the water – permanently installed, with no electricity and no waste water.

Frequently asked questions

Which Drinking Water Ordinance currently applies?

The Drinking Water Ordinance of 20 June 2023, published in the Bundesgesetzblatt (Federal Law Gazette) 2023 I No. 159, currently applies. It has remained unchanged since then. There is no 2025 or 2026 version, but there are provisions of this ordinance that only take effect later.

What changed on 12 January 2026?

Four provisions took effect. Three of them are limit values: sum of PFAS-20 at 0.00010 mg/l, haloacetic acids at 0.060 mg/l and microcystin-LR at 0.0010 mg/l. In addition, the deadline for lead pipes expired.

How many sections does the Drinking Water Ordinance have?

The ordinance has 72 sections in 16 divisions and seven annexes. Its predecessor from 2001 had 25 sections.

Where are the limit values for drinking water set out?

The chemical parameters are set out in Annex 2. Part I lists 18 substances whose concentration remains constant in the network. Part II lists 15 substances that can rise in the domestic plumbing. Microbiological parameters are in Annex 1, indicator parameters in Annex 3.

Are lead pipes now banned?

Lead pipes had to be removed or decommissioned by the end of 12 January 2026. The public health office can extend the deadline, in exceptional cases until 12 January 2036 at the latest. Since 13 January 2026, the operator must prove to affected consumers that it has fulfilled the obligation or holds an extension.

What limit value applies to PFAS in drinking water?

Since 12 January 2026, a limit value of 0.00010 mg/l has applied to the sum of 20 PFAS listed by name. From 12 January 2028, the sum of PFAS-4 at 0.000020 mg/l will be added, covering four particularly critical compounds.

Is there a limit value for legionella?

Instead of a limit value, Legionella spec. has a technical action value of 100 colony-forming units per 100 ml. If it is reached, the operator must report the finding, investigate the causes and prepare a written risk assessment.

Are microplastics and pharmaceutical residues monitored?

Pharmaceutical residues, hormones and microplastics have no limit value in the ordinance. However, § 35(1) no. 7 obliges risk management to include the European watch list. The basis for this is Article 13(8) of Directive (EU) 2020/2184.

Sources

  1. Trinkwasserverordnung, Annex 2 (chemical parameters) and Annex 3 (indicator parameters), reference BGBl. 2023 I No. 159, pp. 48 to 51
  2. Trinkwasserverordnung, § 17 (drinking water pipes made of lead), § 19 (requirements for treatment), § 35 (risk management), § 51 (obligations to act with regard to Legionella spec.)
  3. Directive (EU) 2020/2184 of the European Parliament and of the Council of 16 December 2020 on the quality of water intended for human consumption